DAC M60
A class of compact, lightweight and versatile DAC MV cable test systems with withstand voltage test, PD analysis and PD localization
The “Damped Alternating Current” (DAC) test systems M30, M40 and M60 form an exceptionally compact, lightweight and versatile class of systems for testing and diagnosing Medium-voltage transmission cables. They are programmable and have automatic withstand voltage testing, partial discharge (PD) measurement and analysis as well as PD localization. The controls, measurement and presentation of results is user-friendly, with a common software platform for the entire range of our products.
A DAC cable test does not just provide a rudimentary “good/bad” statement, it is an advanced analysis and diagnostic concept. It enables the condition of the cable insulation to be assessed of newly installed, repaired or in-service cable systems and thus supports the asset management process of the cable operator.
-
Get In Touch For A Consultation
Technical Data
The measurement modes include:
- Withstand voltage test with operating voltage, but also above it
- Partial discharge measurement, analysis and localization along complete cable systems
The DAC voltage test and PD analysis enables the reliable detection of:
- Defects in the cable insulation due to installation or routing
- Defects in the cable fittings, i.e. joints and terminations
- Damage to the cable insulation due to ageing processes
Properties
Compact, easy to transport, versatile in use
Extra
Additional capacity for testing short cables is included
Max. Output voltage
30 / 40 / 60 kV
DAC frequency range
20 – 1000 Hz
Cable length
up to 20 km
PD Resolution
1 pC
Supply voltage
94 – 250 V
Standard
Cable testing according to IEC 60270, IEC60060-3
Addition
PRPDA sample, IEEE-compliant operating andsafetydevice, socket and fault location
UHF Sensors (Drain Valve Sensor)
Partial Discharge Calibrator C-1